Festo 3929314 Positioner CMSX-P-S-C-U-F1-D-130-C
Reference imageConfirm configuration by manufacturer part number.

Festo

3929314

Positioner CMSX-P-S-C-U-F1-D-130-C

This Festo digital, electropneumatic positioner operates in a double-acting mode featuring a safety position with pneumatic outlets closed. It incorporates a linear potentiometer sensing range of 0 deg to 100 deg, a 7-segment backlit LCD display with key-based setting options, and supports an operating pressure range of 3 bar to 8 bar (0.3 MPa to 0.8 MPa) utilizing compressed air per ISO 8573-1:2010 [7:4:4]. Operating on a nominal 24 V DC voltage with a maximum current consumption of 600 mA, the unit includes G1/8 pneumatic connections and analog inputs spanning 0 - 10 V, 0 - 20 mA, and 4 - 20 mA. Submit the exact part number, quantity, and application requirements to request a formal quote for this component.

Request pricing and availabilityCommercial response within one business day for your destination and required quantity.
Request a Quote
Why no listed price?

Industrial and obsolete parts are priced per enquiry: the final price depends on available stock, condition, quantity, and your delivery destination, so a fixed list price would be misleading. Request a quote and we confirm current pricing, lead time, and sourcing options — including hard-to-find and discontinued Festo references — within one business day.

Manufacturer
Festo
Part number
3929314
Data verification
Manufacturer evidence reviewed

For a faster response, include quantity, condition, and delivery destination.

Exact part-number verificationTechnical properties are matched to 3929314.
Worldwide sourcingSupport for planned and urgent industrial requirements.
Manufacturer documentationA document is added when the reviewed source provides one.

Verified configuration

Technical Specifications

Structural design
digital, electropneumatic positioner
Mode of operation
Double-acting
Design features
Safety position - pneumatic outlets closed
Mounting position
Any
Type of mounting
With accessories
Measuring principle of linear potentiometer
Potentiometer
Sensing range
0 deg...100 deg
Display
7-segment | LCD display | With backlighting
Setting options
Via display and keys
Size of dead space
0.5 %...10 %
Operating pressure
0.3 MPa...0.8 MPa | 3 bar...8 bar | 43.5 psi...116 psi
Operating medium
Compressed air as per ISO 8573-1:2010 [7:4:4]
Information on operating and pilot media
Operation with oil lubrication not possible | Maximum particle size 40 µm
Normal nominal ow rate (normalized to DIN 1343)
130 l/min
Pneumatic connection
G1/8
Nominal operating voltage DC
24 V
DC operating voltage range
21.6 V...26.4 V
Max. current consumption
600 mA
Reverse polarity protection
for operating voltage connections
Analog inputs, signal range
0 - 10 V | 0 - 20 mA | 4 - 20 mA
Analog inputs, max. dynamic range
0 - 24 mA | 0 - 11 V
Analog inputs, linearity error at 25°C
0.5%
Analog inputs, temperature coefficient
0.02 %FS/K
Analog inputs, resolution
16 bit
Analog inputs, overload protection
Yes
Analog inputs, galvanic isolation
No

Engineering context

Identification and RFQ Guidance

Confirm the exact configuration

Use the manufacturer part number and model code—not appearance alone. Connection, size, material, voltage, pressure, seal, and control options can differ within the same product family.

What to include in your RFQ

Provide quantity, delivery country and ZIP/postal code, required condition, target date, and photographs of the existing nameplate when available.

Technical verification

Our sourcing response is prepared against Festo 3929314. Final compatibility remains subject to the machine manufacturer’s requirements and complete application data.