Palazzoli 158222 Palazzoli 158222 — Fire-resistant junction box made of reinforced technopolymer with perforated insulation for unipolar cables with socket IEC60309, 1000°C 90'/830°C 120', IP66
Reference imageConfirm configuration by manufacturer part number.

Palazzoli

158222

Palazzoli 158222 — Fire-resistant junction box made of reinforced technopolymer with perforated insulation for unipolar cables with socket IEC60309, 1000°C 90'/830°C 120', IP66

The Palazzoli 158222 is a fire-resistant junction box measuring 275X165X130 mm, constructed from high-resistance technopolymer and stainless steel AISI 304 with an IP66 protection degree and IK10 shock resistance. This Class II component features a 230V AC rated operating voltage, 690 V rated insulation voltage, pierce-through connecting terminals on a ceramic base, and integrated fuse protection utilizing two 8,5x32 fuses for a 2P+T direct output socket. Engineered for unipolar cables with line cable sections of 2,5-50 mm² and tightening diameters of 8÷18,2 mm, the unit provides thermal endurance rated at 1000°C for 90 minutes and 830°C for 120 minutes within a C5-H corrosivity category environment. Submit the exact part number, quantity, and application requirements to receive a quote.

Request pricing and availabilityCommercial response within one business day for your destination and required quantity.
Request a Quote
Why no listed price?

Industrial and obsolete parts are priced per enquiry: the final price depends on available stock, condition, quantity, and your delivery destination, so a fixed list price would be misleading. Request a quote and we confirm current pricing, lead time, and sourcing options — including hard-to-find and discontinued Palazzoli references — within one business day.

Manufacturer
Palazzoli
Part number
158222
Product series
Fire-resistant junction box made of reinforced technopolymer with perforated insulation for unipolar cables with socket IEC60309, 1000°C 90'/830°C 120', IP66
Data verification
Manufacturer evidence reviewed

For a faster response, include quantity, condition, and delivery destination.

Exact part-number verificationTechnical properties are matched to 158222.
Worldwide sourcingSupport for planned and urgent industrial requirements.
Manufacturer documentationA document is added when the reviewed source provides one.

Verified configuration

Technical Specifications

Product Family
Fire-resistant junction box made of reinforced technopolymer with perforated insulation for unipolar cables with socket IEC60309, 1000°C 90'/830°C 120', IP66
Line cable sections
2,5-50 mm²
Insulation Class
II
Dimensions
275X165X130 mm
Protection fusibile
2 fusibile 8,5x32
Code
158222
Net weight
1.12KG
Min order quantity
1
EAN Code
8014950233410
Gross Weight
1.12KG
Direct output
Presa 2P+T
Type of protection
Fuses
Connecting Terminals
Pierce-through on ceramic base
Tightening diameter
8÷18,2 mm
Shock resistance
IK10 according to IEC/EN 62262
Corrosivity category
C5-H (ISO 12944)
IP Protection degree
IP66
Rated operating voltage
230V AC
Rated insulation voltage
690 V
Manufacturing material
Stainless steel AISI 304, High resistance technopolymer
Height Box
53mm
Execution
Wall mounting
Cover type
Blind
Fuse Type
2 Fuse 4 A (L+N)
Cover height
75mm
Colour
Blue RAL 5012 (Cover), RAL 7042 (Base)
Internal dimensions
132X82X64 mm
Resistance to temperature
830°C a 120 minuti
Min. Amb. Temp.
-25°C
Max. Amb. Temp.
+50°C
Storage room temperature MIN
-30°C
Storage room temperature MAX
+70°C
Standards and Directives
EN 60670-1:2005; EN 60309-1:1999; EN 60309-1:1999/A1:2007; EN 60309-1:1999/A2:2012; EN 60309-1:1999/A1AC:2014; EN 60309-2:1999; EN 60309-2:1999/A1:2007; EN 60309-2:1999/A2:2012; EN 60669-1:1999/A2:2008; EN 60670-1:2005/AC:2007; EN 60670-1:2005/A1:2013; EN 60670-22:2006; EN IEC 63000:2018; EN IEC 60331-1:2019; CEI 64-20:2023; DIN 4102-12:1998; 2011/65/EU (RoHS); 2012/19/EU (WEEE); 2014/35/EU (LVD)

Engineering context

Identification and RFQ Guidance

Confirm the exact configuration

Use the manufacturer part number and model code—not appearance alone. Connection, size, material, voltage, pressure, seal, and control options can differ within the same product family.

What to include in your RFQ

Provide quantity, delivery country and ZIP/postal code, required condition, target date, and photographs of the existing nameplate when available.

Technical verification

Our sourcing response is prepared against Palazzoli 158222. Final compatibility remains subject to the machine manufacturer’s requirements and complete application data.